All In Data CenterAll In Data CenterCenter of the ecosystem
Power & Energy
Ultron DPS Series
Delta By Delta

Ultron DPS Series ✓ Verified

The Ultron DPS is Delta's three-phase, four-wire online UPS ranging from 160 to 500 kVA and paralleling up to 4000 kVA, delivering high reliability for large data centers and industrial loads.

Category
Country of Origin
Taiwan
Technology
Three-phase four-wire online double-conversion UPS
Key Features
High parallel capacityUp to 8 units parallel for capacity or redundancy, scaling to 4000 kVA.
High efficiencyUp to 96% double-conversion and 99% ECO-mode efficiency reduce energy cost.
Low harmonic distortionOutput voltage THD kept low (≤1.5% for linear loads) for clean power.
Intelligent monitoringMulti-language LCD with comprehensive status and communication options.
Technical Specifications
Power range
160 to 500 kVA (up to 4000 kVA in parallel)
AC-AC efficiency
Up to 96%
ECO mode efficiency
Up to 99%
Output power factor
0.9 (1.0 optional in select regions)
Output voltage regulation
±1% static
Parallel redundancy
Up to 8 units
Applications
Large data centers Industrial power Infrastructure and utilities
Related Products
← Modulon DPH Series 9900D UPS →